• https://www.orecco.com/wp-content/uploads/2018/06/24KV-GIS-Industrial-Switchgear-570.jpg

24KV GIS Industrial Switchgear

24KV GIS industrial switchgear is one of the types of medium voltage gas insulated switchgear designed for commercial & industrial applications.

24KV GIS industrial switchgear was developed by using full sealed structure concept and modular design. All live components are placed in a sealed stainless steel shell and shall not be affected by external environment to ensure high reliability and safety requirements. In addition, it can be configured as customized automation solution to realize intelligent control.

This GIS industrial switchgear is designed in high degree of standardization level, easy extension, and convenient combination. The left and right sides of the airbox unit can be arbitrarily extended through a dedicated bus connector, which realizes diversification of unit combination and extremely meets user demands for diversification of high voltage power distribution.

With its combination of fixed unit compound mode and flexible expansion, the product is suitable for requirements of ring network power distribution or user terminals and meets the requests of various kinds of compact switchgear flexible usage for secondary substations.

The GIS industrial switchgear can be connected with the automatic system through the communication network to implement the remote control, telemetry and remote signal functions of the switchgear, this intelligent online monitoring, and protection solutions ensure the switchgear working in high technology level.

Ring6 24KV C-module F-module v-module
Switch disconnector Earthing switch Switch-fuse disconnector Downstream earthing switch Vacuum circuit-breaker Earthing switch/ disconnector
Rated voltage kV 12/17, 5/24 12/17,5/24 12/17,5/24 12/17,5/24 12/17,5/24 12/17,5/24
Rated frequency 5) Hz 50/50/50 50/50/50 50/50/50 50/5 0/50 50/50/50 50/50/50
Power frequency withstand voltage kV 284)/38/50 284)/38 /50 284,/38 /50 284,/38 /50 284)/38/50 284)/38/50
Lightning impulse withstand voitage kV 95/95/125 95/95/125 95/95/125 95/95/125 95/95/125 95/95/125
Rated normai current A 6 30/630/630 2001) 200/200/200
Breaking capacities:
-active load A 630/630/630
-closed loop A 650/650/650
-offload cable charging A 140/140/140
-offload transformer A 20/20/20
-earth-fault A 205/160/160
-earth-fault cable charging A 117/91/91
-short-circuit breaking current kA see2) 16/16/16
Marking capacity kA 52,5/40/40 52,5/40/40 see2) 5 12,5/12,5/12, 40/40/40 40/40/40
Short tirne current 3 sec,3) kA 21/16/16 21/16/16 16/16/16 16/16/16

1) Depending on the current rating of the fuse-link
2) Limited by high voltage fuse-links
3) Maximum rating for bushings Interface C (400 series bolted)
4) GOST version is available with 42kV power frequency to withstand voltage
5) For rated frequency 60Hz de-rating for current parameter needs to be applied

CEO Note

Hey! This is Tony, the CEO of Orecco Electric. Thanks for visiting our website and I hope to be a friend with you. I have 20 years experience in electric power transmission for primary distribution and secondary distribution, I would like to share my experience with you in this field, please contact me to discuss when you have any question about our products, I’m happy to help you. I provide free consultant for many clients, and if you need any help on power transmission, reach me any with with blow button.

Related Products

11KV GIS Distribution Switchgear
11KV GIS Distribution Switchgear
15KV GIS Metal Clad Switchgear
15KV GIS Metal Clad Switchgear
33KV SF6 GIS switchgear
33KV SF6 GIS switchgear
SF6 Gas Insulated Substation
SF6 Gas Insulated Substation

Become An Expert When Importing Medium Voltage Electrical Equipments

Here will be the most detailed and professional basics focusing on electrical switchgear.
You could learn the ultimate guide to know the working principle of SF6 gas insulated switchgear from here.
Air circuit breaker and vacuum circuit breaker with the same function as breaking, but their big difference you must know to select the correct one for your project.
Here is the most comprehensive tips for you to know the difference between the power transformer and distribution transformer.
Update cookies preferences
Scroll to Top